Why interlocks prevent fatal mistakes — until people defeat them
Introduction — interlocks exist because people make predictable errors
HV interlocks are not optional safety extras. They exist because history showed that humans will:
- open live compartments
- earth energised conductors
- rack breakers under load
- bypass “just this once”
Interlocks turn unsafe intent into mechanical impossibility — unless someone disables them.
What interlocks are designed to prevent
A properly designed HV interlock system prevents:
- opening breaker compartments when live
- racking breakers under load
- applying earth switches to live circuits
- closing breakers when earthing is applied
- access to cable compartments without isolation
Each interlock blocks one specific fatal action.
Types of interlocks onboard ships
Mechanical interlocks
- Direct physical linkages
- Key-based systems
- Shutter mechanisms
Reliable — but vulnerable to wear and force.
Electrical interlocks
- Auxiliary contacts
- Control logic dependencies
- PMS integration
Flexible — but vulnerable to logic misunderstanding.
Key interlock systems (Kirk / Castell)
Often used in HV rooms to enforce sequence discipline:
- isolate → earth → access
- access closed → de-earth → re-energise
If keys are missing, duplicated, or bypassed — the system collapses.
🔧 Regulatory anchors (explicit)
IEC 60092-503
Requires:
- interlocking to prevent unsafe operation
- protection against incorrect sequence
- visible status of earthing and breaker position
IACS E11
Class expects:
- interlocks functional and not bypassed
- racking operations performed only under defined conditions
- documented racking procedures available onboard
Bypassed interlocks are a Class deficiency.
Racking operations: the highest-risk HV task
Racking a breaker is dangerous because:
- contacts move under spring energy
- arc risk exists during engagement
- fault current capability is highest at close-in
Correct racking requires:
- breaker fully open
- system load removed
- correct alignment
- controlled speed
- PPE appropriate to arc risk
“Just push it in” has killed ETOs.
🔻 Real-World Case: Serious Injury During HV Breaker Racking
An ETO was severely burned while racking a 3.3 kV breaker that was believed to be unloaded. Investigation found:
- interlock defeated due to “operational inconvenience”
- residual load still present
- arc initiated during contact engagement
The breaker closed exactly as designed.
The interlock defeat created the hazard.
The cultural trap: operational pressure
Interlocks are often defeated because:
- shutdown delays operations
- bridge wants power restored fast
- “we’ve always done it this way”
This is where ETO professionalism matters.
No operational urgency justifies bypassing HV safety systems.
Knowledge to Carry Forward
HV interlocks are lessons learned in steel and copper.
If an interlock stops you, it is because someone died before it existed.
Never defeat interlocks.
Never rush racking.
Never trust position indicators without physical verification.
A safe HV system is one that refuses to cooperate with unsafe actions.